fbpx





Series 2000 SteamHigh Pressure Boiler

The High Pressure Series 2000 Steam Boiler is available with firing inputs from 1600MBTU to 2000MBTU. However, millions of BTU’s can be delivered by creating an efficient, fully modular system sequenced by a control panel.

Series 2000 Steam High Pressure Boiler can burn:
Natural Gas, Propane, #2 Oil, Dual Fuel

Contact Sales

Features

  • UL Listed Gas Trains and Control Systems.
  • Power Burners.
  • Pressure Gauge
  • 125 lb Pressure Relief Valve
  • L404F Honeywell Pressure Control
  • L4079B Honeywell High Limit
  • McDonnell Miller 150 Water Level Control
  • Manual Reset Low Water Cutoff
  • Gauge Glass Assembly
  • Honeywell Aquastat Relay
  • Burner Control Relay
  • 2″ Diameter Firetubes of SA178-A Steel
  • Turbulators for Maximum Heat Transfer
  • High performance Insulation With a Painted Steel Jacket.

Standard features include nationally known parts and controls that are quickly available at most supply houses, allowing for quick and easy repair and maintenance, which can dramatically reduce down time.

Options

Superior Boiler offers many options:

  • Choice of burners fired by natural gas, oil, propane, or dual fuel.
  • Modulating gas trains.
  • Fan-Damper relays
  • Clean-out openings and plugs

Design

The Series 2000 Steam Boiler is manufactured to meet ASME Section I standards and is capable of providing operating pressure of up to 125 psi. These vessels contain 70 vertical firetubes, each of which is 2″ diameter, 12 gauge steel, each fitted with a high-efficiency turbulator for maximum heat transfer. The combustion chamber is fully water-backed, with burners that are UL listed.

Safety

A well-made, rugged vessel is naturally a safer boiler. But Superior Boilers also have a combustion chamber design that is completely backed by water, along with well known boiler controls resulting in a very safe and secure package.

5/5 (1 Review)

Series 2000 Steam High Pressure Boiler Drawings

Boiler Efficiencies

Series 2000 Steam, High Pressure
Model
Input (BTU/Hr)
Gross OutPut
HP Output
Combustion Efficiency
GPM @ Riseº F
Steam Output (lbs/hr)
2000
2,000,00
1,620,000
46.1
81.0%
N/A
1,592
2000
1,900,00
1,539,000
43.8
81.0%
N/A
1,513
2000
1,800,00
1,458,000
41.5
81.0%
N/A
1,433
2000
1,700,00
1,377,000
39.2
81.0%
N/A
1,353
2000
1,600,00
1,296,000
36.9
81.0%
N/A
1,273