Series 1600 SteamLow Pressure Boiler
The Series 1600 Steam Boiler is available with firing inputs from 1100MBTU to 1700MBTU. However, millions of BTU’s can be delivered by creating an efficient, fully modular system sequenced by a control panel.
Series 1600 Steam Low Pressure Boiler can burn:
Natural Gas, Propane, #2 Oil, Dual Fuel
Support Documents
Boiler Information
CAD Drawings
Features
- UL Listed Gas Trains and Control Systems.
- Power Burners.
- 0-30 lb Pressure Gauge
- 15 lb Pressure Relief Valve
- P7810C Solid State Pressure Control, Manual Reset
- 150 Water Level Control
- Manual Reset Low Water Cutoff
- Gauge Glass Assembly
- Honeywell Aquastat Relay
- Burner Control Relay
- 2″ Diameter Firetubes of SA178-A Steel
- Turbulators for Maximum Heat Transfer
- One Inch of high performance Insulation With a Painted Steel Jacket.
Standard features include nationally known parts and controls that are quickly available at most supply houses, allowing for quick and easy repair and maintenance, which can dramatically reduce down time.
Options
Superior Boiler offers many options:
- Choice of burners fired by natural gas, oil, propane, or dual fuel.
- Low-High-Low or Modulating gas trains.
- Fan-Damper relays
- Clean-out openings and plugs
Design
The Series 1600 Steam Boiler is manufactured to exceed ASME Section IV standards and is capable of providing operating pressure of up to 15 psi with nominal operating temperature of 218°F to 240°F. These vessels contain 70 vertical firetubes, each of which is 2″ diameter, 12 gauge steel, each fitted with a high-efficiency turbulator for maximum heat transfer. The combustion chamber is fully water-backed, with burners that are UL listed.
Safety
A well-made, rugged vessel is naturally a safer boiler. But Superior Boilers also have a firebox design that is completely backed by water, along with safety controls on the boiler that results in a very safe and secure package.
Series 1600 Steam Low Pressure Boiler Drawings
Series 1600 Steam, Low Pressure
|
||
---|---|---|
Model #
|
HP
|
File
|
1600
|
19.8
|
|
1600
|
32.3
|
|
1600
|
34.7
|
|
1600
|
39.7
|
|
1600
|
42.2
|
Boiler Efficiencies
Series 1600 Steam, Low Pressure
|
||||||
---|---|---|---|---|---|---|
Model
|
Input (BTU/Hr)
|
Gross OutPut
|
HP Output
|
Combustion Efficiency
|
GPM @ Riseº F
|
Steam Output (lbs/hr)
|
1600
|
1,200,00
|
996,000
|
29.8
|
83.0%
|
N/A
|
1,027
|
1600
|
1,300,00
|
1,079,000
|
32.3
|
83.0%
|
N/A
|
1,112
|
1600
|
1,400,00
|
1,162,000
|
34.7
|
83.0%
|
N/A
|
1,198
|
1600
|
1,600,00
|
1,328,000
|
39.7
|
83.0%
|
N/A
|
1,369
|
1600
|
1,700,00
|
1,411,000
|
42.2
|
83.0%
|
N/A
|
1,455
|
Boiler Dimensions
Series 1600 Steam, Low Pressure
|
|
---|---|
Feature
|
Dimension
|
Vessel Width
|
34″
|
Vessel Height
|
77″
|
Boiler Weight
|
1800 lbs
|
Boiler Depth w/ Burner
|
66″
|
Gas Inlet Height
|
12″
|
Return Water Inlet Height
|
9″
|
Height Required at Installation
|
90″
|
Clearance to Front of Boiler
|
48″
|
Clearance to Side of Boiler
|
18″
|
Clearance Between Boilers
|
6″
|
Clearance of Steam Pipe to Vessel Top
|
24″
|