Engineered and
Built to Order

Request a Quote

Let our Problem Solvers quote a boiler designed for your needs. Request a Quote

Give us a call at (620) 662-6693 or EMAIL US

Capacity: 250,000 - 500,000 lb/hr

Fuel Capabilities: Digestor Gas, Fuel Oil, Hydrogen, Natural Gas, Other Fuels

Steam Design Pressure: Up to 1,200 psig

Resources

General Description

Tandem Steam Generating Units-Type Boiler with separate furnace, convection, and superheater module.

Features

  • Superheated steam temperature up to 900°F
  • Patented design incorporates separate furnace, convection, and superheater module
  • Suitable for Natural gas, Oil, and Heat Recovery applications
  • Lower cost of ownership: minimized capital cost and reduced operating costs

Construction

  • Separate Furnace, Convection and Superheater modules for easy transportation
  • Enlarged furnace with uniform heat flux promotes lower emissions
  • 100% Water cooled wall construction
  • Generous convection module with lowest total draft losses
  • Optional superheater module
  • Gas outlet configuration: top, rear, left, or right side

Quality

100% Furnace water-cooled membrane wall construction
Air-tight full membraned front, rear, and side exterior walls
0.25″ thick membrane fin plate
All drilled drum holes are grooved
Minimum tube thickness exceeds ASME requirements:
– 0.105″ min. wall convection tubes
– 0.120″ min. wall furnace tubes
Economizer designed and built by Superior
All ladders and platforms are fit and bolted to boiler then disassembled for shipment

Safety

Packaged boilers are trimmed with necessary safeties and code piping and signed off on by code inspectors. Factory mounted and wired, proven and reliable packaged burners are available from your choice of burner manufacturer.